RTV insulator coating works in Southern Africa’s harshest pollution, and the clearest local proof is the Duinefontein substation on the Western Cape coast. In 2004, this 132 kV substation, about 600 metres from the sea, received a single application of RTV silicone insulator coating. Before that, it flashed over every year. After it, the substation recorded zero flashovers over the next 18 years, including a severe coastal pollution event in February 2006.
That coating was not a CSL product. So this article uses Duinefontein only as proof that RTV silicone technology works. For the coating Technical Solution Supplies (TSS) supplies today, Si-COAT 570 HS (also known as 570 HS), the proof is its own. It passed both IEC TR 62730 tests at independent accredited high voltage laboratories. The full accredited test reports are available on request from Technical Solution Supplies.
What Happened at Duinefontein: RTV Insulator Coating in the Field
Before 2004, the substation suffered flashovers on a yearly basis. In February 1999, it went through a severe Type B instantaneous pollution event, the kind that takes substations offline and damages equipment. Salt, fog and high humidity make that stretch of coast one of the hardest places for porcelain insulators.
Then the insulators received one coat of RTV silicone. Over the following 18 years the site recorded zero flashovers. In February 2006, another severe coastal pollution event hit the area, and the coated substation rode it out. For utilities, that is the point of Duinefontein: one application changed the behaviour of the whole site.
Why Southern Africa’s Insulators Have a Hard Life
No two pollution environments in Southern Africa are the same, but every one of them threatens unprotected high voltage insulators. The KwaZulu Natal coast exposes insulators to constant salt spray, which builds up fast during onshore winds. The Western Cape adds sea fog, which wets the contamination without any visible rain. Duinefontein sits in exactly that environment.
Inland, the Highveld corridor from Mpumalanga through Gauteng carries fallout from coal fired power stations, heavy industry and traffic. The Northern Cape combines extreme UV with heavy dust from arid ground and mining. Further north, the Copperbelt in Zambia and the DRC adds mine dust and chemical fallout. Namibia’s Atlantic coast, meanwhile, brings persistent fog and salt. Still, the failure path is the same everywhere. Contamination builds up, moisture activates it, leakage current flows, dry bands form, and flashover follows.
How RTV Insulator Coating Stops Flashover
The answer comes down to one surface property: hydrophobicity. An uncoated porcelain or glass insulator is hydrophilic, so moisture from rain, fog, dew or condensation spreads across it as a continuous film. That film dissolves salts in the contamination and becomes conductive. Then leakage current flows, dries parts of the surface unevenly and creates dry bands. Arcing across those bands is what escalates into a flashover.
A correctly applied silicone coating makes water bead and run off instead. As a result, the contamination cannot dissolve into one continuous conductive layer, and the leakage current path is broken. In addition, silicone has a property called hydrophobicity transfer. Low molecular weight silicone moves from the cured coating into the dirt that settles on it. So the pollution layer itself becomes water repellent. That is why an RTV insulator coating keeps working as contamination builds up. In light rain, the beading water also carries loose dirt away.
Coating, Washing or Grease: Choosing for Your Site
Washing removes contamination, but it does not change the surface. So the dirt comes back, and the wash has to be repeated, usually with planned outages each time.
Silicone grease is a fair choice on some sites. TSS supplies CSL 880 insulator grease, a non curing silicone compound applied 1 to 2 mm thick, with an anti tracking filler. It is white, so crews can see when it needs replacing. Grease works by holding the pollution in its layer. Once that layer is loaded, crews remove it and apply fresh grease. Therefore it suits sites already on a greasing cycle, or where the utility specifies grease.
An RTV insulator coating suits long term protection. It goes on before energisation or during a planned outage. Then it bonds to the insulator and stays water repellent for years. For most utilities, the choice comes down to site conditions, outage windows and the utility’s own standards.
Si-COAT 570 HS: The RTV Insulator Coating TSS Supplies
Si-COAT 570 HS is a one part RTV silicone insulator coating made by CSL Silicones. It needs no primer, no mixing and no thinning. According to CSL, its patented larger ATH particle differs from the sub micron ATH in competing coatings and limits settling. It goes unprimed onto glass, porcelain, HTV and LSR silicone and EPDM. It also refreshes older silicone coatings once crews clean them. CSL lists it for AC and DC systems at all voltage levels.
The strongest proof is independent. Si-COAT 570 HS passed both tests in IEC TR 62730 at independent ISO/IEC 17025 accredited high voltage laboratories, on coated porcelain line post insulators. First came the 5,000 hour multiple stress test: repeating daily cycles of rain, salt fog, 95% humidity, 50°C heat and simulated sunlight under continuous voltage. The test also ran at a higher voltage than the standard sets for that insulator. The result was no flashovers or trip outs, no puncture, no erosion reaching the core, and insulation resistance above 2 MΩ throughout. Second came the tracking and erosion wheel test, with more than 30,000 cycles of dipping in salt water and energising. Again there was no tracking or erosion to the core and no puncture.
The TDS adds more. Static contact angle is 116° (IEC 62073), and it passes IEC 60587 at 1A 4.5 and 1B 4.5. It also shows no degradation after 5,000 hours of UV and salt fog (IEC 61109), and it lasts more than 1,000 hours on the CEA tracking wheel. Finally, it passes the CEA 100 hour boiling water test and IEEE 957 water blast adhesion. According to CSL, it has more than 15 years of field service with zero failures.
Apply it at about 0.38 mm dry (15 mil, 380 µm), with a minimum of 0.25 mm (10 mil). That is roughly half a litre per square metre before losses. Eskom Transmission’s standards for RTV silicone insulator coatings list several test routes for heavy pollution sites. Both IEC TR 62730 tests are among them. Si-COAT 570 HS holds accredited reports for both, so it meets those test requirements, although approval itself is Eskom’s decision. For Eskom work, apply at least 0.3 mm dry.
Where an RTV Coating Is Not the Answer
An RTV coating does not repair a cracked, chipped or punctured insulator, so damaged units need replacing first. It is not applied live: Si-COAT 570 HS goes on before energisation or during a planned outage. It is also not touch protection for people, and it does not stop animal flashovers. Finally, where a utility specifies grease, grease is the right answer for that site.
Frequently Asked Questions
What is RTV insulator coating?
RTV insulator coating is a room temperature vulcanising silicone coating sprayed onto porcelain and glass insulators to make their surface water repellent. Water beads instead of forming a conductive film, so leakage current and dry band arcing are far less likely to lead to flashover.
Was Duinefontein coated with Si-COAT 570 HS?
No. The 2004 Duinefontein coating was not a CSL product. We quote it only as proof that RTV silicone coating technology works. The proof for Si-COAT 570 HS is its own pass of both IEC TR 62730 tests at independent accredited laboratories.
How long does an RTV insulator coating last?
It depends on the site and the thickness applied. Duinefontein recorded 18 years without a flashover after one RTV application. For Si-COAT 570 HS, CSL reports more than 15 years of field service with zero failures.
Is RTV coating better than silicone grease for insulators?
It depends on the site. Grease such as CSL 880 holds pollution in its layer, and crews replace it once it is loaded. So it suits sites on a greasing cycle or where the utility specifies it. An RTV coating bonds to the insulator and suits long term protection with fewer outages.
Can RTV insulator coating be applied to glass and porcelain?
Yes. Si-COAT 570 HS goes onto glass, porcelain, HTV and LSR silicone and EPDM insulators without a primer. It can also refresh an older silicone coating after cleaning.
Can an RTV insulator coating be applied on live equipment?
No. Crews apply Si-COAT 570 HS before energisation or during a planned outage, by airless spray, brush or dip.
For full technical data, see the Si-COAT 570 HS insulator coating page and the Si-COAT 570 HS FAQ. Our article on coating new substations from day one covers the grid build. Our guide to anti corrosion coating for structural steel then covers the steel around the insulators.
To discuss your site, contact us with photos of the insulators and the pollution they face. You can also ask for the accredited test reports or a site visit.
Technical Solution Supplies distributes CSL Silicones products across Southern Africa, including the DRC and the Seychelles.
Proud exclusive distributor of CSL Silicones in Southern Africa.